水温空调为节能环保带来了福音,顺应了当前发展趋势,但是故障是不可避免的,由于其本身会装有报警器,当出现不同故障时,会有不一样的显示,所以我们可以根据判断做出处理方法。
Water temperature air conditioning has brought the gospel to the energy conservation and environmental protection, complied with the current development trend, but the failure is inevitable, because it will be equipped with a alarm itself, when there are different faults, there will be different display, so we can make a processing method according to the judgment.
一、报警。济南空调维修这种情况就是说明水温空调压缩机处于停机状态,这时不要急于开机,要先排查其他原因有无报警,要是存在按照情况予以解决,要是无其他报警信号,要先检查电压,假如供电系统不达要求,压机是不工作的,假如电压正常再检查启动电容有无损坏,解决后再运行开机。
1. Efficient alarm. Ji'nan air conditioning maintenance this situation means that the water temperature air conditioning compressor is in a shutdown state, do not rush to start the machine, to check other reasons first, if there is no alarm, if there is a solution in accordance with the situation, if there is no other alarm signal, to check the voltage, if the power supply system does not meet the requirements, the press is not working, the press is not working, If the voltage is normal, check whether the starting capacitor is damaged or not, then run it again after it is resolved.
二、报低压。制热时,代表系统内缺氟,这种情况有两种现象。
Two, report low pressure. In the process of heating, there are two phenomena in the system, which are lack of fluorine.
①由于机器处于停机状态,启动后氟处于低温,瞬间蒸发不好导致报低压,这时不要做任何处理,等待几分钟,现象即可消除,恢复正常状态。
(1) because the machine is in the state of shutdown, the fluorine is at low temperature after starting, and the evaporation is not good at the moment, which leads to low pressure. Then do not do any treatment, wait a few minutes, the phenomenon can be eliminated and normal state.
②机器运行时间长导致系统缝开焊外漏,缺少,这时应先检查漏点进行修好,然后按正常生产步骤,进行充氟,正常操作即可。
(2) the long running time of the machine leads to the leakage and leakage of the seam welding of the system. At this time, the leakage point should be checked first, and then the normal operation can be carried out according to the normal production steps.
三、报水流或E1。代表系统内水流显示不够或无水,在这种水流报警的情况下,先把水流开关线短接,开机运行注意出水口温度(制冷时偏高或制热时偏低)变化,判断是否是水流开关坏。假如水流开关坏了,立即更换,然后恢复水流设置,反之,就是系统缺水。
Three. Report water or E1. The water flow in the representative system shows not enough or water. In the case of this water flow alarm, the current switch line is short, and the opening operation pays attention to the temperature of the outlet of the water (when the cooling is high or the heat is on the low side), to judge whether the flow switch is broken. If the flow switch is broken, replace immediately, then restore the water flow. Otherwise, the system is short of water.